Outdoor lighting considerations | Plant Engineering (2024)

Key Concepts
  • Types

  • Mounting poles

  • Aiming

  • Lamp data

  • Illumination levels

    Sections:
    Industrial floodlighting
    Wall lighting
    Decorative pole-top lighting
    Decorative floodlighting
    Horizontal area lighting
    Vertical area lighting
    Cutoff area lighting
    Mounting pole selection
    Floodlight aiming
    Lamp data
    HID characteristics
    Illumination levels

    Whether lighting the front office facade, employee parking lot, storage yard, or flagpole, outdoor lighting requires that plant engineers follow certain guidelines.

    Outdoor lighting should be more than just decorative. Safety, security, functionality, and efficiency should be considered when designing and specifying lighting systems for a plant’s exterior.

    For starters, drive by the plant after dark. Walk from parking lots to buildings. Audit storage yards, entranceways, material handling yards, and other potential work areas, making note of light levels and shadowy areas.

    After identifying the weak areas, inventory the current outdoor lighting array, paying close attention to security or spill-light issues. Surveillance cameras and security personnel depend on adequate lighting. Quantify current lighting levels and determine where it is necessary to supplement or replace fixtures.

    A.

    Industrial floodlighting

    Use industrial floodlighting to illuminate storage yards, tanks, signs, substation and transformer yards, and vital structures.

    B.

    Wall lighting

    Use wall lighting for entranceways, loading docks, signage on sides of buildings, and platforms.

    C.

    Decorative pole-top lighting

    Use decorative pole-top lighting for walkways leading to front offices, access roadways, and driveways.

    D.

    Decorative floodlighting

    Use decorative floodlighting for facades, displays, flagpoles, and corporate signage.

    E.

    Horizontal area lighting

    Use horizontal area lighting for sides of buildings, signage, walkways, entrance approaches, access roadways, and driveways.

    F.

    Vertical area lighting

    Use vertical area lighting for parking lots, sides of buildings, signage, storage tanks, and platforms.

    G.

    Cutoff area lighting

    Use cutoff area lighting to avoid spill light and glare on adjacent properties and roadways. Sharp cutoff lighting is used in medium and large areas such as parking lots, storage yards, and material handling areas that border roadways, walkways, or other plants or property.

    Mounting pole selection

    When lighting horizontal areas such as parking lots and material handling yards, engineers must specify luminaire mounting height on poles, pole height, number of poles for the area to be illuminated, and pole placement.

    The distance between poles should not exceed four times the mounting height. This ratio applies to the distance across a lighted area as well as lateral distance between poles. This guideline applies regardless of the number of floodlights per pole, the level of illumination desired, or the type of light source (incandescent, fluorescent, or HID lamps).

    Center pole systems can be used when lighting large areas at illumination levels up to 5 fc. These center poles should be within a distance of two times the luminaire mounting height from the sides of the area to be illuminated.

    Side poles should be no more than two times the luminaire mounting height from the corners.

    Definition : Footcandle (fc) is a unit of illuminance. One fc is one lumen (lm) per square foot, or: 1 lm/ft 2= 1 fc

    Lighting poles must support the luminaires and their mounting hardware. Poles also must be sturdy enough to withstand the highest wind velocity expected for a given location. Each vendor of outdoor lighting provides selection recommendations based on luminaire type, pole loading, total loading, effective projected area (EPA), and geographic location.

    Floodlight aiming

    Vertical aiming

    General rules for lighting vertical surfaces differ from those for horizontal areas. Illumination uniformity is necessary for vertical surface lighting.

    For normal area lighting, the aiming point should be 2/3 to

    Lighting on vertical surfaces is often as important as horizontal lighting — especially for outdoor work area or security lighting. The vertical illumination in line with the floodlight is determined by this ratio:

    horizontal mounting distance:mounting height

    For example, if the horizontal distance is twice the mounting height, the vertical illumination is twice the horizontal distance.

    Horizontal aiming

    Floodlights with NEMA 6 or 7 horizontal beams effectively light an area at least 45 deg to either side of the aiming line. Perimeter poles require at least two floodlights to cover an area in all directions (Table 1).

    NEMA beam spreads

    NEMA type beam spread Horizontal aiming line separation Recommended max aiming line separation
    218-29 deg12 deg
    329-46 deg24 deg
    446-70 deg40 deg
    570-100 deg60 deg
    6100-130 deg90 deg
    7>130 deg120 deg

    Lamp data

    High-intensity discharge lamps

    According to IEEE, a high-intensity discharge (HID) lamp is an electric discharge lamp in which the light-producing arc is stabilized by wall temperature. Advantages of HID lamps include:

    • High efficiency

    • Long lamp life

    • Good lumen maintenance

    • Compact light source

    • Good light control by using reflectors and refractors.

      • HID characteristics

        HID lamps deionize when the power to them is interrupted or if the lamp socket voltage drops below the amount required to sustain the arc for more than a few cycles. The lamp will not restart immediately because it takes greater voltage to ionize the arc tube vapors while they are hot and under high pressure.

        HID restrike and warmup characteristics

        HID lamp type Time to reach 80% light output Time to restrike
        Mercury5-7 min3-6 min
        Metal halide2-4 min10-15 min
        High-pressure sodium3-4 min1 min

        Illumination levels

        Recommended outdoor lighting levels for industrial plants are based on data published by the Illuminating Engineering Society. Lighting installations should be designed and luminaires selected based on minimum maintained light levels, rather than initial values. Some of the Society’s recommendations are listed in the table to the right.

        PLANT ENGINEERING magazine extends its appreciation to Appleton Electric Co.; Crescent/Stonco; GE Lighting Systems, Inc.; Holophane; and Thomas & Betts Lighting for the use of their materials in the preparation of this article.

        Recommended industrial illumination levels

        Application/location Minimum average recommended illumination, fc
        Building exteriorsSuburbCityRural
        Terra cotta, light marble, or plaster10155
        Bedford or buff limestone, smooth buff face brick, concrete, or aluminum152010
        Smooth or medium-gray brick, common tan, or dark field-gray brick203015
        Brownstone, stained wooden shingles, or other dark surfaces355020
        Application/locationMinimum average recommended illumination, fc
        Building exteriorsSuburbCityRural
        Main plant parking areas222
        Secondary parking areas111
        Active entrances (pedestrian and/or conveyance)555
        Inactive entrances (normally locked, infrequently used)111
        Vital locations or structures555
        Building surrounds111
        Loading and unloading platforms202020
        Substation and transformer yards, horizontal general area222
        Substation and transformer yards, vertical tasks555
        Storage yards, active202020
        Storage yards, inactive111
        Industrial yard, material handling555
        ApplicationMinimum average recommended illumination, fc
        Signs, bulletin/poster boards, and flagpolesSuburbCityRural
        Bright surroundings
        Light surfaces505050
        Dark surfaces100100100
        Dark surroundings
        Light surfaces202020
        Dark surfaces505050
        Coal yards (protective)0.20.20.2

    Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our CFE Media editorial team and getting the recognition you and your company deserve. Click here to start this process.

    Outdoor lighting considerations | Plant Engineering (2024)
    Top Articles
    Latest Posts
    Article information

    Author: Chrissy Homenick

    Last Updated:

    Views: 6518

    Rating: 4.3 / 5 (54 voted)

    Reviews: 93% of readers found this page helpful

    Author information

    Name: Chrissy Homenick

    Birthday: 2001-10-22

    Address: 611 Kuhn Oval, Feltonbury, NY 02783-3818

    Phone: +96619177651654

    Job: Mining Representative

    Hobby: amateur radio, Sculling, Knife making, Gardening, Watching movies, Gunsmithing, Video gaming

    Introduction: My name is Chrissy Homenick, I am a tender, funny, determined, tender, glorious, fancy, enthusiastic person who loves writing and wants to share my knowledge and understanding with you.